offshore-power-and-control-cable

Fire resistant, flame retardant halogen-free power cable. Mud resistant

BFOU 0,6/1(1,2)kV

MGT/EPR/EPR/TCWB/EVA

NEK TS 606 CodeP5/P12

Operating temperature : 90°C
Operating Voltage : 0,6/1(1,2)kV

Application

Fixed installation for power, control and lighting in both
EX (Zone 0, 1 & 2)- and safe areas, emergency and
critical systems where requirement for fire resistance
exists. For installation in areas exposed to MUD and
drilling/cleaning fluids. Meets the MUD resistance
requirement in NEK TS 606:2009.

Standards applied

IEC 60092-353 – Design
IEC 60228 class 2 – Conductor
IEC 60092-360 – Insulation
IEC 60092-360 – Sheath
IEC 60332-1-2 – Flame Retardant
IEC 60332-3-22 – Flame Retardant
IEC 60331-1, -2, -21 – Fire Resistant
IEC 60754-1,2 – Halogen Free
IEC 61034-1,2 – Low Smoke

Construction

Code Letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation R Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Lay up / Shielding Cores laid up in concentric layers
Inner covering F Flame retardant and halogen-free thermoplastic compound
Tape over inner covering PET tape
Armour/screen O Tinned annealed copper wire braid
Tape over armour/screen PET tape
Outer sheath U Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
Marking text E.g. "meter" "year" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX - FLAME IEC 60331-1*) or IEC 60331-2*) IEC 60331-21**) IEC 60332-3-22
Manufacturing unit DRAKA 01 = Draka Norsk Kabel,
Outer sheath colour Black

Core identification power cables

Single core – Black
Two cores – Blue – Brown
Three cores – Brown – Black – Grey
Four cores – Blue – Brown – Black – Grey
Five cores – Blue – Brown – Black – Grey – Black
Seven cores and above – White with black numbers
Two cores + earth (3G) – Yellow/green – Blue – Brown
Three cores + earth (4G) – Yellow/green – Brown – Black – Grey
Four cores + earth (5G) – Yellow/green – Blue – Brown – Black – Grey
G / X in cable description – G = One of the cores are yellow/green – X = no yellow/green core
Core identification – to HD308S2 – and IEC 60445 Ed 5.0 2010-08

Range and dimensions

Offshore-Fire-Resistant-Power-Control-Cable-Range-and-dimensions

Ordering information

Offshore-Fire-Resistant-Power-Control-Cable-Ordering-information

Electrical values power cables

Offshore-Fire-Resistant-Power-Control-Cable-Electrical-values-power-cables

Ambient temperature correction factors

Offshore-Fire-Resistant-Power-Control-Cable-Ambient-temperature-correction-factors

Installation recommendations

Offshore-Fire-Resistant-Power-Control-Cable-Installation-recommendations
Those indicated with(*) represent round conductor
*We reserve the right to alter this specification without prior notice.
offshore-power-and-control-cable-rfou

Fire resistant, flame retardant halogen-free power cable. Mud resistant. Single core cable.

BFOU 0,6/1(1,2)kV

EPR/EPR/TCWB/EVA

MGT/EPR/EPR/TCWB/EVA

Operating temperature : 90°C
Operating Voltage : 0,6/1(1,2)kV

Application

Fixed installation for power, control and lighting in
both EX (Zone 0, 1 & 2)- and safe areas,
emergency and critical systems where requirement
for fire resistance exists. For installation in areas
exposed to MUD and drilling/cleaning fluids. Meets
the MUD resistance requirement in NEK TS
606:2009.

Standards applied

IEC 60092-353 – Design
IEC 60228 class 2 – Conductor
IEC 60092-360 – Insulation
IEC 60092-360 – Sheath
IEC 60332-1-2 – Flame Retardant
IEC 60332-3-22 – Flame Retardant
IEC 60331-1, -2, -21 – Fire Resistant
IEC 60754-1,2 – Halogen Free
IEC 61034-1,2 – Low Smoke

Construction

Code Letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation R Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Lay up / Shielding Cores laid up in concentric layers
Inner covering F Flame retardant and halogen-free thermoplastic compound
Tape over inner covering PET tape
Armour/screen O Tinned annealed copper wire braid
Tape over armour/screen PET tape
Outer sheath U Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
Marking text E.g. "meter" "year" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX - FLAME IEC 60331-1*) or IEC 60331-2*) IEC 60331-21**) IEC 60332-3-22
Manufacturing unit DRAKA 01 = Draka Norsk Kabel,
Outer sheath colour Black

Core identification power cables

Single core – Black
Two cores – Blue – Brown
Three cores – Brown – Black – Grey
Four cores – Blue – Brown – Black – Grey
Five cores – Blue – Brown – Black – Grey – Black
Seven cores and above – White with black numbers
Two cores + earth (3G) – Yellow/green – Blue – Brown
Three cores + earth (4G) – Yellow/green – Brown – Black – Grey
Four cores + earth (5G) – Yellow/green – Blue – Brown – Black – Grey
G / X in cable description – G = One of the cores are yellow/green – X = no yellow/green core
Core identification – to HD308S2 – and IEC 60445 Ed 5.0 2010-08

Range and dimensions

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-Range-and-dimensions

Ordering information

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-Ordering-information

Electrical values power cables

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-Electrical-values-power-cables

Ambient temperature correction factors

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-Ambient-temperature-correction-factors

Installation recommendations

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-Installation-recommendations
Those indicated with(*) represent round conductor
*We reserve the right to alter this specification without prior notice.
Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-epr

Fire resistant, flame retardant halogen-free power cable. Mud resistant. Double braided.

BFOU 0,6/1(1,2)kV

MGT/EPR/EPR/TCWB/EVA

NEK TS 606 CodeP5/P12

Operating temperature : 90°C
Operating Voltage : 0,6/1(1,2)kV

Application

Fixed installation for power, control and lighting in both
EX (Zone 0, 1 & 2)- and safe areas, emergency and
critical systems where requirement for fire resistance
exists. For installation in areas exposed to MUD and
drilling/cleaning fluids. Meets the MUD resistance
requirement in NEK TS 606:2009.

Standards applied

IEC 60092-353 – Design
IEC 60228 class 2 – Conductor
IEC 60092-360 – Insulation
IEC 60092-360 – Sheath
IEC 60332-1-2 – Flame Retardant
IEC 60332-3-22 – Flame Retardant
IEC 60331-1, -2, -21 – Fire Resistant
IEC 60754-1,2 – Halogen Free
IEC 61034-1,2 – Low Smoke

Construction

Code Letter
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation R Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Lay up / Shielding Cores laid up in concentric layers
Inner covering F Flame retardant and halogen-free thermoplastic compound
Tape over inner covering PET tape + rubberized Polyamide tape
Armour/screen O Two layers of tinned copper wire braid (double braid)
Tape over armour/screen PET tape + rubberized Polyamide tape
Outer sheath U Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
Marking text E.g. "meter" "year" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX - FLAME IEC 60331-1*) or IEC 60331-2*) IEC 60331-21**) IEC 60332-3-22
Manufacturing unit DRAKA 01 = Draka Norsk Kabel
Outer sheath colour Black

Core identification power cables

Single core – Black
Two cores – Blue – Brown
Three cores – Brown – Black – Grey
Four cores – Blue – Brown – Black – Grey
Five cores – Blue – Brown – Black – Grey – Black
Seven cores and above – White with black numbers
Two cores + earth (3G) – Yellow/green – Blue – Brown
Three cores + earth (4G) – Yellow/green – Brown – Black – Grey
Four cores + earth (5G) – Yellow/green – Blue – Brown – Black – Grey
G / X in cable description – G = One of the cores are yellow/green – X = no yellow/green core
Core identification – to HD308S2 – and IEC 60445 Ed 5.0 2010-08

Range and dimensions

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-epr-Range-and-dimensions

Ordering information

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-epr-Ordering-information

Electrical values power cables

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-epr-Electrical-values-power-cables

Ambient temperature correction factors

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-epr-Ambient-temperature-correction-factors

Installation recommendations

Offshore-Fire-Resistant-Power-Control-Cable-BFOU-mgt-epr-Installation-recommendations
Those indicated with(*) represent round conductor